Chiller Performance Measurement

Overview
The performance assessment of the chiller plant involves calculation of cooling duty delivered by the system and measurement of power consumed by the unit. The Specific Power Consumption (SPC - kW/TR) and Energy Efficiency Ratio (EER) are the effective measures for comparing the electrical energy input to cooling duty delivered by the system. The study involves measuring various parameters such as flow rate, temperature and power in the both chilled water and refrigeration side of the chiller system.
Refrigeration Effect
Formula
- Refrigeration Effect (TR) = (Flow(Q) × Cp × (Ti – T0)) / 3024
Where:
- Q = Flow Rate m3/s
- Cp = Specific Heat kcal/kg deg C
- Ti = Inlet Temperature (Deg C)
- T0 = Outlet Temperature (Deg C)
Scope of Work
Case Study
Energy Conservation Measures
- Maintain the chiller Specific norms and reduce the chiller consumption by Overhaul of the Existing Chiller
Calculation
| SN | Parameter | Unit | Chiller |
|---|---|---|---|
| 1 | Actual Chiller Capacity Requirement | TR | 103.34 |
| 2 | Existing Specific energy consumption of screw chiller | kW/TR | 0.81 |
| 3 | Suggest Specific energy consumption of screw chiller | kW/TR | 0.70 |
| 4 | Specific Energy Consumption Saving | kW/TR | 0.11 |
| 5 | Power Saving | kW | 11.58 |
| 6 | Electrical unit cost | Rs/kWh | 9.57 |
| 7 | Daily working hour | hr | 24.00 |
| 8 | Annual Operating Day | Day | 330.00 |
| 9 | Annual Power Saving | kWh | 91693 |
| 10 | Annual Monetary saving | Rs | 877067 |
| 11 | Investment of Overhaul Water Cooled Screw chiller | Rs | 600000 |
| 12 | Simple Payback period | Month | 8.21 |
Explore Related Services
View All Services →
Energy Audit is defined as “the verification, monitoring and analysis of use of energy including submission of technical report containing recommendations for improving energy efficiency with cost benefit analysis and an action plan to reduce energy consumption”. It builds on the principle "you can't manage what you don't measure". It essentially combines the principles of energy use and statistics.

Energy conservation is the effort made to reduce the consumption of energy by using less of an energy service. This can be achieved either by using energy more efficiently (using less energy for a constant service) or by reducing the amount of service used (for example, by driving less).

Harmonic analysis is a technique used to study and analyze the harmonic components in a periodic waveform or signal. The main use of harmonic analysis in electrical engineering is to examine the existence and properties of harmonics in electrical power systems. Harmonic voltage or current waveform frequencies are integer multiples of the fundamental frequency. However, due to non-linear loads, such as power electronics, variable speed drives, and certain types of lighting, harmonic currents and voltages can be introduced into the system.

A compressed air audit effectively identifies inefficiencies, reduces energy costs, and improves system performance. Many industrial air compressors operate inefficiently due to leaks, artificial demand, and incorrect air pressure requirements, unnecessarily increasing cost per kWh.